Fire Resistant and Flame Retardant Cable and Wire

The Characteristic and Usage of the Products

The copper conductors pliable fire resistant and flame retardant cable for use of the emergency system exploited and manufactured by our Corporation can maintain the circuit integrity when the fire situation occur, and can ensure that the vital function of emergency system operate well and safety.

Recently, this kind of products have being used widely abroad for the center commercials, hospitals, offices, stations, airports, dwellings and others buildings for connection of fire alarm system, smoke detectors system, emergency lighting and power supply system and public address system.

The sketch map of the application of the products

This new kind of fire resistant and flame retardant cable have remarkable characteristics as below:

1. to compare with the traditional fire resistant and flame retardant cable, the emission of smoke and acid gas is less than the traditional cable, when exposed to fire, particularly, with the water and with the mechanical shock, the cable can still maintain the circuit integrity, i.e. the circuit can operate normally.

2. to compare with the mineral insulating fire cable, the new kind cable have too many advantage as below:

a. because the new kind of fire resistant and flame retardant cable adopt the pairs or twisted core construction, the signal clarity and transmission rates are improved remarkably.

b. With it¡¯s screen structure, the anti-electro-magnetic interference performance is massively improved, particularly, over the frequency range 1--100MHz, attenuation improvement of 30--35db is achieved over unscreened cable.

c. The new kind cable have much lower core to core and core to screen capacitance than other conventional fire resistant cable, the growth of systems allowing longer cable runs makes the new cable ideal for fire alarm circuits where low capacitance is vital.

d. The new cable is pliable, no limit for manufacturing length, diminishing the point of termination of circuit, no requirement of many components and specialized and expensive tools, rising the installation speed and reliability.

3. the new kind of fire resistant and flame retardant cable meet the highest categories of BS6387 ¡°performance requirements for cables required to maintain circuit integrity under fire conditions¡± i.e. C, W and Z. The symbol C means that under fire condition 950¡æ for 3 hours energized at the rated voltage, no puncture occurs. The symbol W means that under fire condition 650¡æ for 15 minutes then for 15 minutes with fire and water energized at the rated voltage, no puncture occurs. The symbol Z means that under fire condition 950¡æ for 15 minutes with 30 seconds hammer blows energized at the rated voltage, no puncture occurs.

4. the physical characteristic:

a. voltage rating (U0/U):300/500v.

b. operating temperature: -40¡æ--+90¡æ(the cable should not be flexed when either the ambient or cable temperature is below 0¡æ).

c. Minimum bending radius: 6¡Áoverall diameter of cable.

5. standards achieved:

a. circuit integrity: passes BS6387 categories C, W and Z. passes IEC331-3hours at 750¡æ.

b. Smoke and acid gas emission: passes GB/T17650-1998.

c. Smoke density: passes GB/T17651-1998.

 

BS6387
IEC-331
categories
Resistance to fire test
Temperature
¡æ
Time
h
Temperature
¡æ
Time
h
650
3
No
No
-
750
3
750--800
3
-
950
3
No
No
C
950
1/3
No
No
-
Resistance to fire and water test
650
1/2
No
No
W
Resistance to fire with mechanical shock test
650
1/4
No
No
-
750
1/4
No
No
-
950
1/4
No
No
Z

 


Resistance to fire test

Resistance to fire with mechanical shock test

Resistance to fire and water test

The Type and specification

The type of the new kind of fire resistant and flame retardant cable is HJLZ, taking the first letter of four Chinese words: the Huozai (fire-H), Jingbao (fire alarm-J), lianjie (connection-L), and Zuran (flame retardant-Z). The E of the table below means protective Earth conductor (tinned annealed copper), the section is the same with the conductors of insulated phase cores (the class1 or class 2). The cable can also be supplied with steel wire armor protection.

Conductor CSA mm2
1.0
1.5
2.5
4
6
No.of cores n+E
£¨2¡¢3¡¢4¡¢7¡¢12¡¢19£©+E
£¨2¡¢3¡¢4£©+E

Current ratings and associated volts drop of cable installation:

Current ratings and associated volts drop
(conductor operating temperature 70¡æ)
Phase conductor CSA

mm2
2cores+E
(single phase ac or dc)
3-4+E (3 phase)
Current rating
A
Volt drop
mV
Current rating
A
Volt drop
mV
1.0
15
44
13.5
38
1.5
19.5
29
17.5
25
2.5
27
18
24
15
4.0
36
11
32
9.5
6.0
46
7.3
41
6.4

The fire resistant type control and power cable:

The fire resistant type power cable
The fire resistant type control cable
Conductor CSA mm2
No.of cores n
Conductor CSA mm2
No.of cores n
4-185
1-5
1.0-4.0
2-36

 

The name:Jiangsu Yuantong Cable Co.,Ltd.
Address:Wenyou North Road,the Economic development area,
Gaoyou Municipality,Jiangsu Province
Post code:225600
Tel:0514-4612490
Fax:0514-4612490
Email:cableyt@yahoo.com,webmaster@cableyt.com
http://www.cableyt.com
Contact person:Chen Ming


Back Home

Copyright JIANGSU YUANTONG CABLE Co.,LTD.2005 all rights reserved
Site designed and hosted by
gaoyou.com,Email:webmaster@gaoyou.com

You are visitor